Reliable Controls Corporation

MACH-ProCom Building Controller, MPC

Type:  Controller
Description:  The MACH-ProCom(tm) is a 32-bit based BACnet? device that delivers unprecedented value in a high performance building controller. The MACH-ProCom(tm) provides high speed 10/100 Ethernet, SMART-Net communications, expandable I/O, and protocol support for BACnet?, RCP, SMTP, and Modbus RTU and TCP (both master and slave). The MACHProCom(tm) controller database allows users to define up to 160 universal I/O on a single address. Points are added to the MACH-ProCom(tm) using MACH-ProPoint(tm) I/O expansion modules, up to 8 of which can be added to each MACH-ProCom(tm) controller.
Connectivity:  Modbus, Modbus TCP
Features:  BACnet? Protocol - B/IP x 2, Ethernet, MS/TP and PTP RCP, Reliable Controls Protocol (RCP) for backward compatibility with previous generation systems; SMTP Protocol - Provides standard email communications for broadcasting email alarms; Modbus RTU and TCP in both master and slave configurations; 96 Inputs - Universal ranges, expandable using MACH-ProPoint(tm) expansion modules; 64 Outputs - Universal ranges, expandable using MACH-ProPoint(tm) expansion modules; 256 Variables - Selectable standard and custom ranges plus fixed program-driven values; 64 PID Loops - Standard P, PI, or PID controllers for closed loop control, BACnet loops supported
Specifications:  100 MHz, high-performance 32-bit embedded microcontroller; Memory - 8 MB operating RAM, 1 MB non-volatile RAM (trends and dynamic values), 2 MB Flash EEPROM operating system, database, and controller config; Supply Voltages - 24 VAC/VDC, 20 VA max; Communications - IEEE 802.3 Ethernet 10/100 BaseT, 2 EIA-485 @ 76.8 kbps max., 1 EIA-232 @ 115.2 kbps max. PC or modem, SMART-Net port @ 16 sensors max.; I/O Expansion Modules - Up to 8 MACH-ProPoint(tm) expansion modules with 12 universal inputs and 8 universal outputs each, 12-bit ADC inputs, 12-bit DAC outputs; Real-Time Clock - ?1 second per day; Memory/RTC Backup - 72 hour backup, 10 years for database