Note: You are seeing this text-only version of our site because you are using an older browser that is not standards-compliant.
How to upgrade to a FREE standards-compliant browser.
Some Netscape 7 and Mozilla users may see this warning in error. Click here to fix the problem.

Modbus Organization

Advantages of Joining | Join Form | Toolkit | Subscribe to Newsletter

Text Size: smallmediumlarge
 Back to Company

 

Continental Control Systems, LLC

WATTNODE MODBUS, WNC-3Y-XXX-MB, WNC-3D-XXX-MB

Type:  Monitoring Hardware
Description:  The WATTNODE® MODBUS is a kW hour/kWh energy meter that communicates on an EIA RS-485 network measuring 1, 2, or 3 phases or loads with voltages from 120 to 600 volts AC and 5 to 6000Amps in Delta (phase to phase) and Wye (phase to neutral) configurations. The Modbus interface networks AC power measurement, true RMS power and energy, energy and demand metering, kWh reactive power, VARs, power factor, line frequency providing both individual and combined phase measurements.
Connectivity:  Modbus RTU
Features:  Low profile - compact dimensions; pluggable screw terminals; line powered; .5% nominal accuracy; uses low voltage CTs; CE Certified; UL and cUL Listed; measures 1, 2, or 3 phases, allows up to 127 WATTNODES per RS-485 subnet; low cost; measurement of true RMS power; reactive power; power factor; true RMS energy; reactive energy; AC frequency; RMS Voltage; RMS current; demand; peak demand.
Specifications:  Modbus RTU; EIA RS-485 interface; baud rates; 9600 and 19,200; response time: 5-300 milliseconds; operating Voltage 0 -.5 VAC; power line frequency - 50-60Hz; 1,2,or 3 phase; Delta and Wye configurations.